Solid fuel boiler BURNiT WBS Magna


от 5 800,00 лв.

Steel solid fuel boilers satisfy the heating demands of large sized spaces as public and industrial buildings. Owing to its smart design WBS Magna is easy to transport and install in spite of its dimensions. Direct connection to closed or open loop heating system. Ready for fitting with pellet burner.

Tested and approved according to EN 303-5.

Features

Maximum operating pressure of 4 bar
Easy installation
Demountable housing
Thermostatic draught regulator
Eyepiece for viewing

Features:

  • Maximum operating pressure of 4 bar.
  • Capable to feed a large-scale heating system.
  • Combustion chamber with large heat exchanging surface and low chamber resistance.
  • The combustion chamber features three-pass flue-gas flow. The mantle fully covers the flue exhaust tubes for optimal heat transfer.
  • Large firebox door ensures easy loading even with bigger logs (up to one meter long).
  • Convenient inspection door in the upper part of the boiler ensures easy cleaning of the flue exhaust tubes.
  • Thermostatic draft regulator for combustion control.
  • Eyepiece for viewing the combustion process.
  • Demountable housing.
  • Flange on the loading door for fitting of pellet burner.

Available sizes, kW:

  • WB MAGNA 250 – PELL 150
  • WB MAGNA 250 – PELL 300

Safety devices

  • Thermostatic draught regulator;
  • Chimney draught flap.

Elements:

1 – Hot water outlet
2 – Safety line
3 – Housing
4 – High efficiency thermal insulation
5 – Fume exhaust tube
6 – Water mantle (jacket)
7 – Three-pass flue gas flow
8 – Combustion chambe
9 – Metal grate
10 – Transportation openings
11 – Air intake door
12 – Burner flange (option)
13 – Loading door
14 – Inspection door
15 – Cold water inlet

Technical characteristics

WBS MAGNA WBS 160 MAGNA WBS 250 MAGNA
rating kW 160 250
Min. / Max. power kW 100÷160 200÷250
height H mm 1800 2150
Width L / D Depth mm 850/1880 950/2070
Volume water jacket L 500 790
Volume combustion chamber L 350 560
Resistance combustion chamber Pa/mbar 23/0.23 23/0.23
Required chimney draft Pa/mbar 42/0.42 42/0.42
recommended fuel wood, wood
briquettes; coal
Max. length of wood loading m 0,8 1
Time to burn partially /
full load
h 4.5/3.0 5.5/3.5
Operating temperature range / Max. temperature °C 65÷85 /95
Temp. the source gases servant. regime °C 120÷150 150÷180
Working pressure bar 4 4
Weight without insulation
insulated
kg 1100
1170
1550
1630
Login cold water А, mm DN 80/250 DN 80/245
Exit hot water B, mm DN 80/1880 DN 80/2100
safety line K1, mm
K2, mm
DN 40/1880
DN 40/500
DN 40/2100
DN 40/500
chimney F, ø/mm
J, mm
ø250/1480
425
ø300/1730
475
Manhole chimney O1, mm
O2, mm
1270
1270
1450
1450
Pipe valve for adjusting the draft G yes yes
Loading door N, mm 450x400 520x580
Inspection door P, mm 820x735 920x850
Door for regulating the inlet air R, mm 460х230 600х230
Thermostatic draft regulator T, mm 1250 1450
draining Y1/Y2, mm G1”/150 G1”/150
Eyepiece for monitoring the combustion process V yes yes
Hole assembly burner (optional) Z yes yes
Do NOT follow this link or you will be banned from the site!